Bartlett V6-CF 700 Control Manual

 

Introduction

     This manual covers the operation of the V6-CF series 700 kiln controller. The V6-CF is a versatile controller that regulates the temperature in your kiln so you can fire a variety of products like ceramics, glass, or jewelry. The experienced operator can go straight to the quick start guide. The novice can learn more about different types of firing by reading the programming sections of the manual. In the following pages:

  • First Firing steps you through the initial firing for new kilns to "season" the elements.
  • Controller Front Panel is a visual table-of-contents for the function of each key on the face-plate.
  • Cone Fire is the quick, easy method of programming for ceramics.
  • Vary Fire (also known as ramp-hold) is the versatile programming method for writing your own profiles for glass, jewelry and ceramics.

The other sections of the manual will answer questions about what to expect during a firing.

Precautions

The controller is used to control temperature, it is not a safety device.

Do not operate the controller in temperatures above 125 °F.

Never leave your kiln unattended at the end of a firing.

The controller contains electronic components which are sensitive to static electricity. Before handling the controller dissipate any static charge you may have by touching metal or a screw on the controller panel, the electrical box, the kiln lid, or some other grounded object.

Always check the position of the thermocouple probe before starting a firing. The current temperature displayed on the controller is measured at the end of the thermocouple.

Always review the current program before firing to ensure the correct profile is programmed.

Ensure the kiln and the areas around the kiln are clear of combustible material. See kiln manufacture's recommendation on required clearances.

Controller Front Panel

START-STOP button for starting and stopping firings.

VARY-FIRE programming for setting and saving your own firing profiles.

OPTIONS section for setting delay start and alarm. Set one of nine "Other" options: Default resetr, Preheat stage time, Controller ID, 16 segment program, Cone offset, Change *F to *C, set Error codes off, set T/C offset, check board temperature.

LED DISPLAY - four digit display showing times and temperature.

NUMBER KEYS section for entering temperatures and times.

CONE FIRE section for choosing one of four preset cone fire speeds.

VIEW section to look up cone temperatures, review the selected program, view the current segment, or skip to the next firing segment

Quick Start

  1. Read all precautions before using your controller.
  2. Apply power to the kiln/controller
  3. Clear the display and get to the idle mode by pressing ENTER.
  4. Program the controller.
  5. Review the program before firing to ensure the correct program is ready to fire.
  6. Press Start. -On- will be displayed and then the kiln temperature. The relays and elements will be cycled on and off to regulate the temperature according to the program.
  7. At the end of the firing the controller will flash the current temperature, firing time, and CPLt. Press ENTER to return to the IdLE state.

IMPORTANT PROGRAMMING NOTE: Before initiating a firing profile or performing any other function, the current temperature must be flashing. Pressing the "1" key will clear the display of errors ('Err') or 'FAIL'.

In most cases when programming, you will choose an option, then press "ENTER" to accept the option. After programming is complete press the "START/STOP" button to begin the firing.

With the display flashing 'IdLE' and the current temperature, you are ready to proceed to one of the programming sections.

The CONE FIRE mode uses Orton's patented method to achieve correct heat work so it is ideal for firing ceramics. The advantage of using the CONE FIRE method is that a very complicated firing profile may be chosen with just a few key strokes. The CONE FIRE method helps protect against over and under firing by carefully tracking and controlling the temperature at the end of the firing as the cone temperature is approached. The final temperature is adjusted according to the final firing rate. For example, as the heating elements age and the heating rate slows, the final temperature will be adjusted downward to ensure the correct amount of heat-work.

The VARY-FIRE mode can be used for ceramics, glass, jewelry, glazes, decals, etc. It allows you to create your own firing profiles which can be saved and used over and over.

Programming

1. CONE FIRE


The CONE FIRE mode allows you to fire to a cone number with one of four different speeds.

To use CONE FIRE:

  1. Make sure the temperature is flashing. Pressing the "1" key will clear the display of errors (Err) or FAIL.
  2. Press one of the 4 firing speed buttons (see Appendix A to see the ramp speeds)

     Slow Bisque - Used for setting a slow bisque firing profile.
             ** 13 hours to fire to cone 04. **

    Fast Bisque - Used for setting a fast bisque firing profile.
             ** 10 hours to fire to cone 04. **

    Slow Glaze - Used for setting a slow glaze firing profile.
             ** 7 hours to fire to cone 04. **

    Fast Glaze - Used for setting a fast glaze firing profile.
             ** 4 hours to fire to cone 04. **

  3. Press ENTER.
  4. Type the cone number you want (acceptable values are from .022 to 10).
    If you type a wrong number, press "0" 3 times or until all zeros appear in the display, press ENTER, then type the correct number (only three digits are displayed at this time)
  5. Press ENTER.
  6. Type the hold time at the end of the firing or leave at zero
  7. Press ENTER. 'CPL' will be displayed briefly, then the current temperature will be flashing in the display.
  8. Press START/STOP to begin firing.

NOTE: With any of the CONE FIRE modes, a preheat stage is available. During the preheat stage the temperature is increased at a rate of 60°F per hour until 200°F is reached; the 200° temperature is then held for the programmed amount of time. Preheat is automatically set to zero during cone fire programming and at the end of each firing, so if a preheat stage is wanted, it must be reprogrammed before each cone firing. See SECTION 4 - "OTHER" options for programming "Preheat".

CONE FIRE Example

Slow Bisque Firing, Pre-heat 1 hour, Cone 04, 10 minute Hold - Use the following steps for a bisque firing to cone 04, a 10 minute temperature hold at the peak temperature, and a preheat stage with 1 hour hold time.

Step Press Display Comment
1 Slow Bisque S-bC If you press the wrong button, before pressing ENTER, simply press the correct button.
2 ENTER alternately flashing:
ConE & No.
Slow Bisque is now selected. The word ConE and the last entered cone number will alternately flash on the display. Now enter the cone number - 04.
3 0, 4 alternately flashing:
ConE & 04
The word ConE and the entered cone number will alternately flash on the display. If you type a wrong number, press zero 4 times, then type the correct number.
4 ENTER alternately flashing:
HLd & 00.00
The cone number has been accepted. Now enter the 10 minute hold time.
5 1, 0 00.10 Numbers to left of decimal point are hours, to the right of decimal point are minutes. If you type a wrong number, press zero 4 times, then type the correct number.
6 ENTER CPL flashes, then the current temperature The 10 minute hold time is accepted. CPL indicates the firing profile has been completed.
7 OTHER until PrHt displayed PrHt Press OTHER until PrHt is displayed. If you accidentally pass PrHt press "OTHER" several more times until PrHt appears again.
8 ENTER alternating flashing:
HLd & 00.00
Preheat has been selected and the hold time is to be entered now.
9 1, 0, 0 01.00 Numbers to left of decimal point are hours, to the right of decimal point are minutes.
NOTE: For a 1 hour hold time you could also enter 60 for 60 minutes; the display would show 00.60. If you type a wrong number, press zero 4 times, then type the correct number.
10 ENTER CPL flashes, then current temperature Accepts a hold time of 1 hour, then CPL indicates the preheat stage has been completed.
11 START/STOP -On- After -On- is displayed for several seconds, the heating elements of the kiln will cycle on and the current temperature in the kiln will be displayed.
If a time is displayed instead of the current temperature, then a delay start is in effect. If you do not want to delay the start press START/STOP button, then DELAY, then 0000, ENTER. When the current temperature again flashes in the display, press START/STOP.

2. VARY-FIRE

The V6-CF has 6 vary-fire user programs to store and reuse. Each program has from 1 to 8 segments (2 - 16 segments if 16-s option is on). Each segment has a firing rate, a soak temperature and a hold time. It is best to write out the firing profile that you plan to program before you begin programming. To ramp at the maximum rate either up or down, enter a rate of 9999. To program a down ramp, you enter the rate/hour then a temperature below the previous segment temperature.
NOTE: The first ramp rate of any user program

The following example is a two segment program stored in memory location "user 1".

Segment Rate °F/hour Temperature Hold
1 100 200 0
2 500 1575 0

 

VARY-FIRE Example
The following steps are used to program "user 1" program for the firing profile above.

Step Press Display Comment
1 ENTER PROG alternately flashing:
USEr & No.
The display alternates between USEr and the last selected user number.
2 1 1 Selects user (USEr) profile number 1
3 ENTER alternately flashing:
SEG & No.
The displays flashes between SEG and the number of segments which were previously programmed
4 2 2 This is the number of segments needed for our example
5 ENTER Alternately flashing:
rA 1 & No.
The display flashes between rA 1 and the heating rate per hour that was previously programmed
6 1, 0, 0 0100 Displays the selected rate/hour
7 ENTER Alternately flashing:
°F 1 & No.
The display flashes between °F 1 & the temperature previously programmed
8 2, 0, 0 0200 Displays the selected temperature
9 ENTER Alternately flashing:
HLd1 & No.
The display flashes between HLd 1 & the hours and minutes which were previously programmed
10 0 00.00 If display does not show 00.00, press 0 until 00.00 is displayed.
11 ENTER Alternately flashing:
rA 2 & No.
The display flashes between rA 2 & the heating rate previously programmed
12 5, 0, 0 0500 Displays the selected rate/hour
13 ENTER Alternately flashing:
°F 2 & No.
The display flashes between °F 2 & the temperature which was previously programmed.
14 1, 5, 7, 5 1575 Displays the selected temperature
15 ENTER Alternately flashing:
HLd2 & No.
The displays flashes between HLd2 & the previously selected hold time.
16 0 00.00 No hold time.
17 ENTER Alternately flashing: ALAr & No. The display alternates between ALAr & the previously used alarm setting.
18 9, 9, 9, 9 9999 Enters the temperature at which the alarm will sound. The alarm will be turned OFF with a setting of 9999.
19 ENTER CPL flashes then the current temperature CPL flashes several times indicating the program has been completed. The current temperature then flashes in the display.

RECALL PROGRAM is used to recall a previously programmed firing profile.
Example: To recall user program #5, use the following:

Step Press Display Comment
1 RECALL PROG Alternately flashing:
USEr & 1
The controller is ready to accept the desired user number.
2 5 5 Indicates the user program selected.
3 ENTER CPL flashes then the current temperature CPL flashes several times indicating the program has been selected. . The current temperature then flashes in the display.

3. VIEW SECTION


View Section - Contains buttons to look up Cone Temperatures, Review programs, View current segment and Skip segments during firings.


The VIEW section allows you to view various information about cone temperatures, firings, and settings.

Cone Table - Used to look up the temperature of various cone numbers. The temperature which is displayed is for self-supporting cones with a heating rate of 108°F/hr. TO use, press "Cone Table", enter the cone number you want to look up, press "ENTER"; the cone temperature will be displayed followed by CPL.

Review Program - The information displayed when Review Program is pressed varies depending on whether you are using Cone Fire or Vary Fire. When Review Program is pressed, each of the steps in the current firing profile is displayed one after another changing every 1/2 second.

In Cone Fire Mode - The display will show the selected firing profile in the following order:

  1. cone fire speed
  2. preheat time (PrHt)
  3. cone #(ConE)
  4. cone temperature* (°F)
  5. hold time (HLd)
  6. delay time (dELA)
  7. alarm setting (ALAr)
  8. error codes on/off (ErCd)
  9. LAG setting (if zone control)

*After a firing is complete, the cone temperature (°F) will show the actual temperature reached during firing.

In Vary Fire Mode - The display will show in the following order:

  1. the user program # (USEr)
  2. the number of segments (SEG)
  3. 1st ramp rate (rA 1)
  4. 1st segment temperature (°F 1)
  5. 1st hold time (HLd1)
    (If there is more than 1 segment, then the ramp rate, segment temperature, and hold time of each of the other segments will be displayed in order.)
  6. delay time (dELA)
  7. alarm setting (ALAr)
  8. error codes on/off (ErCd)
  9. LAG setting if zone control

View Segment - only functions when a firing is in progress. View segment is used to view the current firing segment or to skip from the current segment to the next firing ramp. When View Segment is pressed during a firing the current segment of the firing, the travelling set-point and the circuit board temperature are displayed. If it is pressed during IdLE, StOP is displayed then the current temperature.
Skip Step (SStp) - Skip Step (Skip Step) is included in View Segment. The skip step feature is only available in a VARY-FIRE firing profile. It is used when enough heat work has been done at the current segment and you want to immediately go the next ramp rate. To skip to the next ramp, press View Segment, then within 1/2 second, press ENTER, and ENTER a second time. If you press View Segment and do not press ENTER within 1/2 second, the current segment (e. g., rA 1) will continue to be displayed. Simply wait until the temperature is again displayed and press View Segment, then ENTER within 1/2 second, and ENTER again. If you press View Segment, then ENTER, then decide not to skip to the next ramp stage, simply do not press any key; after about 10 seconds the display will return to the current temperature.

4. OPTIONS SECTION

Delay - This key is used to delay the start of a firing.

Example: Program a one hour delay to the start of a firing.
Remember: the temperature must be flashing before beginning to program.

Step Press Display Comment
1 DELAY Alternately flashing:
dELA and 00.00
The controller is ready to accept the delay time of 1 hour.
2 1, 0, 0 01.00 Displays the selected time. Numbers to left of decimal point are hours, to the right of decimal point are minutes. If you type a wrong number, press zero 4 times, then type the correct number.
3 ENTER CPL flashes then the current temperature CPL flashes several times indicating the 1 hour delay has been accepted. The current temperature then flashes in the display.

Alarm - This key is used to set the high or low temperature alarm. The alarm may be set before or during a firing. When the alarm temperature is reached, a buzzer will sound.

Example: Before the start of a firing, set the alarm temperature to go off at 200°F.
Remember: the temperature must be flashing before beginning to program.

Step Press Display Comment
1 ALARM Alternately flashing:
ALAr and #
The word ALAr and the last entered alarm temperature will alternately flash on the display. The controller is ready to accept the alarm temperature. If no alarm is entered within 10 seconds, the display will flash CPL and then the flashing current temperature.
2 2, 0, 0 0200 Displays the selected temperature of 200°. If you type a wrong number, press zero 4 times, then type the correct number.
3 ENTER CPL flashes then the current temperature CPL flashes several times indicating the alarm temperature has been accepted. The current temperature then flashes in the display.

Other - There are nine "Other" options. Pressing "Other" will continue to cycle through the options available, Rset (reset), PrHt (Preheat), Id (identification), 16-S (16 segment), CnoS (Cone Offset) , CHG° (Change °F to °C), ErCd (Error Codes), tcoS (thermocouple offset), bd t (board temperature), and LAG (LAG setting).
NOTE: PrHt (Preheat) will not appear in this menu unless a CONE FIRE mode has been selected. 16-S will not appear unless User 5 is the selected program.

TO EXIT this menu without selecting any option, cycle through by pressing "Other" until CHG° appears, then press ENTER twice.

rSEt (RESET) press "OTHER" until rSEt is displayed, then press "ENTER". CPL will be displayed indicating that the T/C offsets have been set to zero, the LAG to 13, and the error codes are turned ON.

PrHt (Preheat) - Preheat is used with the CONE FIRE mode only. When Preheat is in use, the temperature ramps up at 60°F/hour to 200°F and then holds at 200° for the amount of time programmed. So if you start at a room temperature of 70°F, then it will take just over 2 hours to reach 200°F at which time the hold will start. Preheat is automatically set to zero during cone fire programming and at the end of each firing. If a preheat stage is desired, it must be reprogrammed for each firing.

Preheat Example: Set a preheat time of 2 hours.
Remember: the temperature must be flashing to start the programming.

Step Press Display Comment
1 Other PrHt If PrHt does not show on the display, even after cycling through the options, it means that a CONE FIRE mode has not been selected. Exit the menu and select a CONE FIRE profile, then return to the Other menu.
2 ENTER Alternately flashing:
HLd & 00.00
Preheat has been selected; enter the time you want to hold the temperature at 200°F (in this example 2 hours)
3 2, 0, 0 02.00 Displays the selected time of 2 hours. Numbers to left of decimal point are hours, to the right of decimal point are minutes. If you type a wrong number, press zero 4 times, then type the correct number.
4 ENTER CPL flashes then the current temperature CPL flashes several times indicating the 2 hour preheat time has been accepted. The current temperature then flashes in the display.

Id (identification #) - Used by KISS (Kiln Interface Software System) to identify the kiln when hooked to a personal computer. This is covered in a separate KISS manual.

16-S (16 segment program) - This option allows vary-fire programs 5 and 6 to be combined into a 16 segment program. It only shows in the menu when user 5 is programmed and selected. When using this option, user 5 and 6 can have 1 to 8 segments. First, program user 5 then user 6. Next, recall user 5 and then use the "OTHER" key to display '16-S'. Press "ENTER" to accept the option. Press "1" until the display shows 'On'. Press "ENTER" to activate the 16 segment option. Press "START" and the controller will fire user 5 until complete and then will fire user 6.
NOTE: The first segment of user 6 must be an up ramp or the segment will be skipped.

The cone-fire to ramp-hold feature allows for the firing of a cone-fire program automatically followed by the User #6 ramp-hold (vary-fire) program. Turning on the 16-segement (16-S) option after programming the cone-fire program activates this feature.
IMPORTANT NOTE: The controller uses the first segment of User 6 to transition from the cone fire program so the controller ignores the first segment. This means when you program, the number of segments you enter must be 1 greater than the actual number of segments you need. In other words, start the actual programming with segment number 2. The controller will ignore any information you enter into segment 1.

Press "Enter Prog" button. Press "6" and then press "ENTER" to program User 6 with desired program.
Segment 1 of User 6 is utilized by the controller and connot be used for your program. Therefore the number of segments will need to be one greater than the number used for programming. When the display showr 'ra 1' press "ENTER", "ENTER", "ENTER" to begin programming segment 2. After User 6 is programmed, press the desired Speed button (S-BC, F-BC, S-GL, or F-GL) in the Cone Fire options. Enter desired Cone-Fire program. Press the "Other" button until '16-S' appears and press "ENTER". The display will flash between '16-S' and the current setting, either 'On' or 'OFF'. Press the "1" key until the desired option is diplayed. Pressing "ENTER" when 'On' is displayed will allow Cone-Fire to flow into Ramp-Hold User 6 and 'OFF' will disable this option, meaning only the cone-fire program will fire. Press the "ENTER" button. Programming is now complete. If 16-segment is on then the controller will perform the Cone-Fire program and upon finishing it will run the Ramp-Hold User 6 program.
NOTE: 16-S will appear in "REVIEW PROGRAM" if it is turned on.

 

CnoS (Cone Offset) - Used to raise or lower the final cone temperature. The final cone temperature can be raised or lowered a maximum of 50°F (28°C).
 

When entering the offset temperature the following convention is used: the left two digits designate whether to raise (00) or lower (90) the cone temperature, that is, '00' means plus (+) and '90' means minus (-). The right two digits are the number of degrees the cone temperature will be raised or lowered.


Examples:

Number Meaning
0020 Raise the final cone temperature by 20°F      increases heat work
0040 Raise the final cone temperature by 40°F           "           "       "
0015 Raise the final cone temperature by 15°F           "           "       "
9030 Lower the final cone temperature by 30°F   decreases heat work
9005 Lower the final cone temperature by 5°F           "           "       "
9045 Lower the final cone temperature by 45°F         "           "       "

The following apply to cone offsets:

  • The final temperature is affected only for the cone number that you change and no other cone numbers.
  • The cone offset will remain for that specific cone number until it is changed again.
  • Typing 00 (before the desired offset temperature) will raise the final temperature and INCREASE the amount of heat work.
  • Typing 90 (before the desired offset temperature) will lower the final temperature and DECREASE the amount of heat work.
  • The maximum number of degrees that can be raised or lowered is 50°F (28°C)
  • Cone offsets do not affect the VARY-FIRE mode.

Cone Offset Example: Adjust cone 07 to shut off the kiln at 20°F below Orton's prescribed cone temperature.

Step Press Display Comment
1 Other, Other CnoS If CnoS does not show on the display, press the "Other" key until "CnoS" displays.
2 ENTER Alternately flashing:
ConE & #
Cone Offset has been selected; the word ConE and the last entered cone number will alternately flash on the display. Now enter the cone number which you want to adjust (in this example cone 07)
3 0, 7 Alternately flashing:
ConE & 07
The word ConE and the entered cone number (07) will alternately flash on the display. If you type a wrong number, press zero 3 times, press ENTER, then type the correct number.
4 ENTER Alternately flashing:
°F0S & 9000
°F OS and the previous offset setting alternately flash. Enter the new offset temperature using the rules above, in this example, "9020".
5 9, 0, 2, 0 9020 The selected offset temperature is displayed. If you type a wrong number, press zero 4 times, then type the correct number.
6 ENTER CPL flashes then the current temperature CPL flashes several times indicating the offset temperature adjustment has been accepted. The current temperature then flashes in the display.

 

tCoS (Thermocouple Offset) - Used to raise or lower the temperature indicated by the thermocouples. The maximum offset is 50°F (28°C). A positive offset is entered with 00 preceding the amount of offset and a negative offset is preceded by 90. This is the same as is done for entering cone offsets. A negative offset will lower the indicated temperature reading and cause more heat-work. When tCoS is displayed, press ENTER and the current offset for the thermocouple will be displayed. Press ENTER when the correct offset is displayed.

The following apply to T/C offsets:

  • The final temperature is affected for all CONE FIRE and all VARY-FIRE programs.
  • The thermocouple offset will remain for that T/C until it is changed again.
  • Typing 00 (before the desired offset temperature) will raise the indicated temperature but it will lower the actual temperature in the kiln and LOWER the amount of heat work.
  • Typing 90 (before the desired offset temperature) will lower the indicated temperature but it will increase the actual temperature in the kiln and INCREASE the amount of heat work.
  • The maximum number of degrees that can be raised or lowered is 50°F (28°C).
  CONE Offset T/C Offset
To Correct Under-firing Set positive (00) cone offset Set negative (90) t/c offset
To Correct Over-firing Set negative (90) cone offset Set positive (00) t/c offset

CHG° - Used to select degrees Fahrenheit (°F) or degrees Celsius (°C).

Example: Change from °F to °C.

Step Press Display Comment
1 Other, Other CHG° If "CHG°" does not show on the display, press the "Other" key until "CHG°" displays.
2 ENTER °F Indicates that the Fahrenheit (°F) scale is being used. You can toggle back and forth between °F and °C by pressing the "1" key.
3 1 °C . Displays "°C .". The decimal point in the lower right corner means that the Celsius (centigrade) scale has been selected.
4 ENTER CPL flashes then the current temperature CPL flashes several times indicating the temperature scale has been changed. The current temperature in °C then flashes in the display. There will be a decimal point in the lower right-hand corner of the display.

 

ErCd - Used to turn on or turn off the error codes. When you receive your controller the error codes are turned on. In most cases, you want the error codes on to protect your firing. They can be turned off if you are doing special firings, such as jewelry or glass firing where the kiln is left open.
NOTE: When ErCd is turned OFF. When errors are off, Err6 (t/c backwards) is still on. In cone fire mode during the last segment (i.e., last 250 degrees) of the firing, Err1 (ramping too slow) and Err8 (temperature falling) are turned on. Error Codes "off" also turns the "LAG" feature off.


Example: Turn the error codes off.

Step Press Display Comment
1 Other, Other ErCd If 'ErCd' does not show on the display, press the "OTHER" key until 'ErCd' displays.
2 ENTER On Indicates that the error codes are turned on. You can toggle back and forth between on and off by pressing the "1" key.
3 1 OFF Displays 'OFF' indicating the error codes will be turned off.
4 ENTER CPL flashes then the current temperature CPL flashes several times indicating the error codes are off. The current temperature then flashes in the display.

bd t (circuit board temperature) - Press "ENTER" when 'bd t' is displayed and the circuit board temperature will be displayed. It is used for diagnostics. If 'FAIL' is displayed indicating a failed thermocouple (t/c), press the "OTHER" key until 'bd t' is displayed, press "ENTER". If the t/c is faulty then the displayed temperature will be approximately room temperature. If the circuit board has failed then 'FAIL' will continue to be displayed.

Hot Keys while the kiln is firing.
      #5 Key - pressing the number 5 key will show the calculated rate of rise. If the kiln has been on for less than 8 minutes, the display will show the programmed rate of rise and not the actual rate.
      #8 Key - pressing the number 8 key will cause three of the display decimal points to act as pilot lights for the elements. The thousands decimal point will light when the top element is on, the hundreds decimal point will light when the middle elements are on, and the tens decimal point will light when the bottom elements are on. When you have a single zone control kiln (one thermocouple) the decimal points will light in unison although there might be some slight variation when each of the decimals come on.

Zone Control

Your kiln must have multiple thermocouples and be wired for multiple zones to take advantage of these features

1. FEATURES AND ENHANCEMENTS

  • 3 separately controlled zones (3 t/c inputs, 3 outputs)
  • Adjustable offsets for each thermocouple (t/c)
  • Continues to fire with 1 or 2 failed thermocouples (t/c's)
  • Slow ramping when any zone lags the set-point
  • Reset function which zeros the t/c offsets, turns the errors on, and sets the lag to 13 degrees

2. GENERAL DESCRIPTION

The V6-CF advanced 3-zone control system is programmed the same as the single zone control but it has new features to ensure even firing from the top to the bottom of the kiln. A 3-zone control has 3 temperature sensor inputs (thermocouples) and 3 independent outputs so the kiln can have 3 separately controlled sections (zones). The controller senses the temperature in each section of the kiln, compares the temperature to the desired temperature (traveling set-point) and adjusts the power going to each section separately giving each just the right amount of power to keep the temperature at the correct setting. The single zone controller only measures the temperature at the center of the kiln and gives all sections the same amount of power.

3. AUTOMATIC LAG FUNCTION

Lag refers to when the temperature of a kiln's section "lags" behind the traveling set point because the programmed ramp rate is faster than the kiln's temperature can rise. The V6-CF series 700 will slow the ramp rate when a section of the kiln lags. The ramp rate determines the amount of "lagging" that is allowed before the firing rate is slowed. Fast ramp rates (>500 °F/hr) will allow the greatest temperature difference between sections. Slow ramp rates (<70 °F/hr) will have the smallest temperature difference between sections. Therefore, when the controller is programmed to go fast it will sacrifice evenness to obtain speed. Likewise, when the controller is programmed to go slow, the controller will maintain tighter control. The controller will try to balance speed and tight control when a medium speed is programmed.

4. THERMOCOUPLE OFFSETS (see Cone offsets and T/C offsets in the OPTIONS SECTION for more information)

Normal variation in thermocouples (t/c) can cause a section to fire too hot or too cool. The zone control has an offset feature to adjust the reading of each thermocouple to compensate for any error. For example, if shelf cones indicate that the bottom section is under firing, it means that the controller thinks the bottom section actually reached the ending temperature when it really was below the ending temperature. To correct this problem, a negative thermocouple offset is required. This offset will be subtracted from the actual reading and will lower the temperature reading in that section. A negative offset will cause a section to fire to a higher temperature increasing the heat-work for that section. A positive offset will cause a section to fire to a lower temperature decreasing the heat-work for that section. To return all t/c offsets to zero, press Menu, "RSET" will be displayed, press ENTER; RSET also turns the error codes (ERCd) on.

5. THREE THERMOCOUPLES

Besides better measuring of the temperature, the zone control also offers security through its three thermocouples. With a single zone controller, a firing will be stopped if the thermocouple (t/c) fails. The zone control with 3 t/c's, will continue to fire if one or two of its thermocouples fail during a firing. If the top or bottom thermocouple fails, that section will be controlled by the middle t/c. If the middle thermocouple fails the middle section will be controlled by the top t/c. If the controller is at "IdLE" and a t/c fails, the display will alternate between FAIL and the number of the failed t/c (1,2,3). The temperature of each zone can be viewed. The temperature will alternately flash with the currently selected zone. To select zone 1, press the "1" key and TC 1 will alternate with the current zone 1 temperature. For zone 2 press the "2" key, for zone 3 press the "3" key.

 

Appendix A: Cone Fire Temperature Profiles

Firing Profile for cone 04

Slow Bisque Firing Profile

Slow Glaze Firing Profile

Segment

Rate F/hr

Temperature

Hold

Time

Segment

Rate F/hr

Temperature

Hold

Time

3

80

250

0

2

5

150

250

0

1

4

200

1000

0

4

6

400

1676

0

4

5

100

1100

0

1

7

120

1926

0

2

6

180

1676

0

3

 

 

 

0

 

7

80

1926

0

3

 

 

 

0

 

 

 

 

Total

13

 

 

 

Total

7

Fast Bisque Firing Profile

 

Fast Glaze Firing Profile

 

Segment

Rate F/hr

Temperature

Hold

 

Segment

Rate F/hr

Temperature

Hold

 

3

120

250

0

2

6

570

1676

0

3

4

300

1000

0

3

7

200

1926

0

1

5

150

1100

0

1

 

 

 

0

 

6

180

1676

0

3

 

 

 

0

 

7

108

1926

0

2

 

 

 

0

 

 

 

 

Total

10

 

 

 

Total

4

 

APPENDIX C: Common Questions and Situations

Q.  During programming of a firing, I typed a wrong number. How do I correct this?

A.   Before pressing ENTER, enter zero until all zeros are displayed, then enter the correct number. If you have already pressed ENTER, you must press enter to progress through to the end of the program then start the program again.

Q.  How do I clear the "PF" from the display?

A.  Press the "1" key. After several seconds the current temperature will be displayed. Several other numbers or STOP may be displayed before the current temperature.

Q.  What does it mean when "FAIL" is displayed?

A.   Most likely the t/c (thermocouple) is defective. See P. 18 ("bd T", board temperature) to determine if the t/c or circuit board is at fault. If the t/c is faulty, it may actually be poor connections on any extension wire rather than the t/c itself. For type K thermocouples check all connections and ensure that yellow wires are connected to yellow wires and red to red all the way from the circuit board to the t/c in the kiln. It is a good idea to loosen the screw connections and then retighten them to break any oxide that may have built up. When connecting the thermocouple, connect the RED wire to the connector with RED dot and connect the YELLOW wire to the connector with the "+". On type "K" thermocouples, the RED wire is always negative, and the YELLOW wire is positive. On type "S" thermocouples the RED wire is negative and the BLACK wire is positive.

Q.  How can I find out the final temperature that was reached during a cone firing?

A.   At the end of a cone fire, the firing time and CPLt will be flashing alternately in the display. Press "STOP". Then press "Review Program", the final temperature will display after oF. This final temperature will be retained until the next firing or until the controller is reprogrammed or turned off..

Q.  What is a segment?

A. A segment is the basic building block of a program either in cone-fire or vary-fire (ramp/hold). Each segment consists of a ramp rate in degrees per hour, a temperature you want to achieve, and whether you want to hold there or not. For example, a program for drying ware going at 60o/hour to 200oF and holding for 2 hours would be a one segment firing, the ramp is 60, the temperature is 200, and the hold is 2.00.

Q.  Do I need to use witness cones for each firing?

A. After checking your kiln with witness cones for the first few firings, if you are satisfied with the results you are getting and how even the kiln is from top to bottom then you do not need to use cones in each firing. It is a good practice to periodically place witness cones in the kiln to check for proper firing. If you suspect a problem or your results have changed then it is a good idea to check the operation of the kiln with witness cones.

 

E-MAIL